CoePower Active Harmonic Filter in einem großen Einkaufszentrum installiert

Projektübersicht

The equipment installation site is a large shopping mall, Dies ist in verschiedene Ausstellungs- und Verkaufsbereiche wie Einkaufszentren -Werbetafeln unterteilt, lighting, supermarkets, exhibition counters, usw. A large number of single-phase loads and LED lighting and LED advertising display light equipment are used. These equipment generate a large number of The third harmonic of the system is superimposed in the N-phase cable of the system, causing a huge current in the N-phase cable of the system and causing cable heating.

Distribution system diagram

Governance effect analysis
Current data

Before the active harmonic filter is turned on, the load current waveform at the lower end of the incoming line switch deviates from the sinusoidal waveform. The effective value of the A/B/C three-phase current is about 170A, and the N-phase current is about 270A.

Before the active harmonic filter is turned on, the load current waveform at the lower end of the incoming line switch is processed and restored to a sinusoidal waveform. The effective value of the A/B/C three-phase current drops to about 150A, and the N-phase current drops to about 30A.

Before the active harmonic filter equipment is turned on, the total harmonic current distortion rate of the load current at the lower end of the dual power switch is about 65%, and the main harmonic distortion orders are 3/5/7 harmonic current distortion.

After the active harmonic filter is turned on, the total harmonic current distortion rate of the load current at the lower end of the switch drops to about 5%, and the 3/5/7 major harmonic distortion times all drop significantly.

After installing our active harmonic filter (Ahf), the harmonic current distortion rate of the load at the lower end of the 0.4KV low-voltage side switch in the shopping center has been significantly improved. The current flowing through the N phase has increased from about 270A to the initial level. , down to 30A, which greatly ensures the safety and stability of the system and reduces the occurrence of N-phase cable heating, Isolierung altern, and fire hazards.

Tags: Ahf, Aktiver harmonischer Filter, active harmonic filter equipment, Lieferanten, Hersteller, Fabrik, Großhandel, kaufen, Preis, Zitat, Schüttgut, zu verkaufen, Unternehmen, Aktie, kosten.

Verwandte Produkt:

Aktiver harmonischer Filter

Teilen Sie den Beitrag:

Verwandte Beiträge

Aktualisieren Sie Cookies -Einstellungen

Fragen Sie nach einem schnellen Angebot

Wir werden Sie in kontaktieren 1 Arbeitstag, Bitte achten Sie auf die E -Mail mit dem Suffix "Sales@coepower.com".