Project background
The hospital’s equipment was tested, and analysis of the test data revealed that the THDi generated by accelerators, X-ray machines, and gastrointestinal machines was approximately 50 %—60 %; Ct (tomografia computerizzata), MRI, and DSA (digital subtraction angiography) were approximately 30%; electronic testing equipment and operating rooms were between 10% E 15%; and frequency conversion equipment was approximately 35%.
Soluzione armonica

Two transformers are on site, each of which needs to be equipped with a 150A filtro di potenza attivo device.
Selezione dell'attrezzatura: Filtro di potenza attivo (APF)
Modello dell'attrezzatura: CoEpo APF/150-0.4-D*2
Metodo di governance: trattamento locale
Capacità di installazione: 300UN
Metodo di installazione: Tipo di rack
Posizione dell'installazione: Sala di distribuzione dell'energia
Effetto
Two 150A active power filters can effectively control the 3rd, 5th, 7th, and 11th order current harmonics.
Active power filters have a fast response speed, full compensation response speed ≤10ms, harmonic compensation capacity of 2~50 times, and flexible configuration. According to the actual power quality status of the system, the control priority can be set to maximize the module utilization.