Project background
The hospital’s equipment was tested, and analysis of the test data revealed that the THDi generated by accelerators, X-ray machines, and gastrointestinal machines was approximately 50 %—60 %; CT (computed tomography), MRI, and DSA (digital subtraction angiography) were approximately 30%; electronic testing equipment and operating rooms were between 10% 그리고 15%; and frequency conversion equipment was approximately 35%.
고조파 솔루션

Two transformers are on site, each of which needs to be equipped with a 150A 유효 전원 필터 device.
장비 선택: 유효 전원 필터 (APF)
장비 모델: CoEpo APF/150-0.4-D*2
거버넌스 방법: 지역 치료
설치 용량: 300에이
설치 방법: 랙 유형
설치 위치: 발전실
효과
Two 150A active power filters can effectively control the 3rd, 5th, 7th, and 11th order current harmonics.
Active power filters have a fast response speed, full compensation response speed ≤10ms, harmonic compensation capacity of 2~50 times, and flexible configuration. According to the actual power quality status of the system, the control priority can be set to maximize the module utilization.